Forum topic by Tyler posted 607 days ago 866 views 1 time favorited 19 replies Add to Favorites Watch
View Tyler's profile

Tyler

52 posts in 613 days


607 days ago

i have a wood stove i got that i want to hook up in my shop, i know it needs to be atleast 18 in away from combustables, i saw the stove pipe at lowes that is single wall and looks like it connects together with a lip in the back seem…has anyone else used this or have an opinion on it?

-- You can get alot further with a kind word and a hand gun, than just a kind word alone


19 replies so far

View bondogaposis's profile

bondogaposis

2446 posts in 952 days


#1 posted 607 days ago

It works fine for interior use. You will want triple wall to go through the roof and outside, and a thimble for the ceiling.

-- Bondo Gaposis

View Don W's profile

Don W

14645 posts in 1169 days


#2 posted 607 days ago

Both Dave and I just did it, http://lumberjocks.com/superdav721/blog/32810

I just don’t have any pictures.

-- Master hand plane hoarder. - http://timetestedtools.com

View Fred Hargis's profile

Fred Hargis

1646 posts in 1094 days


#3 posted 607 days ago

That sounds like snaplock, and you only use it in the room. At the ceiling you would want to transition to a triple wall type of pipe that would go through the attic/roof, to the chimney cap. At the roof you will need the appropriate flashing/storm collar. Take a look at the illustration in the link, it shows the parts.

-- I long for the days when Coke was a cola, and a joint was a bad place to be (Merle Haggard)

View Tyler's profile

Tyler

52 posts in 613 days


#4 posted 607 days ago

awesome i have a aluminum building aand almost the same exact stove shown in the link above, what type of pipe did you use in the link sheet metal?

-- You can get alot further with a kind word and a hand gun, than just a kind word alone

View shipwright's profile

shipwright

4843 posts in 1399 days


#5 posted 607 days ago

Check local codes or you may not have insurance. the stove may have to meet standards, the pipe will have to meet standards and the clearance distances, materials may differ from those of the manufacturer. I love wood stoves and have always had them even on my boats but you have to respect them and in buildings anyway, you gotta watch the code.

-- Paul M ..............If God wanted us to have fiberglass boats he would have given us fiberglass trees. http://prmdesigns.com/

View grizzman's profile

grizzman

6798 posts in 1904 days


#6 posted 607 days ago

ive already gone through this several years ago, the single wall is ok if its inside but where you go through the wall and for exterior use, you want stainless double or triple wall stainless steel pipe, the single wall will not hold up more then a couple of years, it will rust and deteriorate and you will be faced with replacing all of your pipe, there it goes from the stove out the wall needs to be at least double wall, this pipe gets very hot and you could easily set your building on fire if you dont use the thimble and the right pipe..the stainless pipe is expensive, but if your going to do this right, that is what you should use..just my 2 cents on this subject.. and an added P.S, do as paul suggested, what shipwright said, check your local code, you dont want to have a fire and have no insurance when they see you used the wrong pipe…i love my wood stove and i love it even more knowing its piped correctly…..

-- GRIZZMAN ...[''''']

View Tyler's profile

Tyler

52 posts in 613 days


#7 posted 607 days ago

i will def look into that before i get started, can i do stainless all the way threw? from stove to finish?

-- You can get alot further with a kind word and a hand gun, than just a kind word alone

View Tyler's profile

Tyler

52 posts in 613 days


#8 posted 607 days ago

this

is the woodstove and my new shop that im starting to get things together in.

-- You can get alot further with a kind word and a hand gun, than just a kind word alone

View JesseTutt's profile

JesseTutt

795 posts in 712 days


#9 posted 607 days ago

I don’t have a stove in my shop, but I have a fire pit on my wooden deck. I built a platform with the top being concrete board and 1.5” spacing below. The fire pit sits on that. I also placed a piece of concrete board between the fire pit and the deck’s railing. Insurance adjusters have seen it and not had any comments. Actually, I asked one if there were any problems with the fire pit on the deck and he said no. This is Allstate in Missouri.

As others have said, you really need to verify what your local government requires. I would also suggest that you get a couple of quotes from licensed contractors for them to install. Even if you don’t use them you can usually get information on how it should be done.

I don’t have a stove and have never invested much effort in investigating the double walled pipes, but I would be asking if it would be better to run a double walled pipe closer to the stove in the workshop. That way if something were to hit, land or contact the stove pipe there might be better protection the a hot single wall pipe.

-- Jesse, Saint Louis, Missouri

View jumbojack's profile

jumbojack

1152 posts in 1225 days


#10 posted 607 days ago

A good portion of your heat comes from that single wall pipe.

-- Made in America, with American made tools....Shopsmith

View grizzman's profile

grizzman

6798 posts in 1904 days


#11 posted 607 days ago

you can run the double wall or triple if you want from the stove, ive seen it done that way, but i have also seen the single wall used until it goes through the ceiling or wall, the single wall let you get more heat into your shop and its not exposed to the rain when its used indoors so it will last longer inside, so you do have several safe ways to do it, but doing as stated above where you get someone to give quotes, then you can ask questions and figure out how and what you need, and if you think you can do it yourself, then you save some money, but make sure its all good and safe, as you dont want to loose your building or your tools from a bad install..i think you pretty much get what were saying here…good luck and enjoy your stove and being warm in your shop..

-- GRIZZMAN ...[''''']

View Don W's profile

Don W

14645 posts in 1169 days


#12 posted 607 days ago

That stove will heat that building with no problem. You’ll be opening the door to let heat out. I agree, be safe. The most important part is through the wall or ceiling and roof.

-- Master hand plane hoarder. - http://timetestedtools.com

View Tyler's profile

Tyler

52 posts in 613 days


#13 posted 607 days ago

thanks for all the input ill post more pics on my journey to get my shop up and running

-- You can get alot further with a kind word and a hand gun, than just a kind word alone

View Biff's profile

Biff

126 posts in 615 days


#14 posted 607 days ago

I’ve got single wall inside and out. Replacing it every couple years is not a big deal but if I ever get a good deal on insulated pipe I would buy it.

I also recently put in a waste oil drip..wow, I wish I had done that years ago. Fires burn hotter, longer and are easier to start.

-- Interested in Oregon property? Visit me at http://www.willamettepropertiesgroup.com

View Don W's profile

Don W

14645 posts in 1169 days


#15 posted 607 days ago

Biff, How does the waste oil drip work? Where did you get it?

-- Master hand plane hoarder. - http://timetestedtools.com

showing 1 through 15 of 19 replies

Have your say...

You must be signed in to reply.

DISCLAIMER: Any posts on LJ are posted by individuals acting in their own right and do not necessarily reflect the views of LJ. LJ will not be held liable for the actions of any user.

Latest Projects | Latest Blog Entries | Latest Forum Topics

HomeRefurbers.com

Latest Projects | Latest Blog Entries | Latest Forum Topics

GardenTenders.com :: gardening showcase