table saw relocation

  • Advertise with us

« back to Power Tools, Hardware and Accessories forum

Forum topic by jody495 posted 08-21-2016 12:48 AM 491 views 0 times favorited 5 replies Add to Favorites Watch
View jody495's profile

jody495

36 posts in 2343 days


08-21-2016 12:48 AM

hello,I hope someone can help me determine what I need to relocate my table saw. I can’t determine how much amperage my 3hp /220 volt saw pulls.also I need to know what size wire to use and do I need to use 20 or 30 map breakers. the saw will be about 45 feet from the breaker box. any help would be appreciated.


5 replies so far

View nightguy's profile

nightguy

213 posts in 385 days


#1 posted 08-21-2016 12:57 AM

Jesse, hard to read sideways!!! I think in your second pick it sez Max AMB 40,not a P though, looks like a B.But again lousy pics, cant see sideways or all of the tag, Amps should be on it. Look up Ohms Law and do some simple math.

View Redoak49's profile

Redoak49

2639 posts in 1711 days


#2 posted 08-21-2016 01:09 AM

I think that FLA refers to full load amps so 17.9 amps.

View Nostradamit's profile

Nostradamit

38 posts in 560 days


#3 posted 08-21-2016 01:12 AM

I believe the FLA on your tag means “Full Load Amperes”
This might be helpful

View jody495's profile

jody495

36 posts in 2343 days


#4 posted 08-21-2016 01:45 AM

don’t know why the pictures came out side ways.oops.thanks for the information

View TheFridge's profile

TheFridge

7482 posts in 1209 days


#5 posted 08-21-2016 01:54 AM

30A breaker with #10 wire. 3 wire receptacle. NEMA 6-30 im pretty sure.

-- Shooting down the walls of heartache. Bang bang. I am. The warrior.

Have your say...

You must be signed in to reply.