21 replies so far
|
#1 posted 1544 days ago |
If your going to do it I would get a fish tape. Run that through the conduit then tape the rest of the wires and pull all 3 at once. I’m not sure how well it will fit (in terms of code correct for fill size). You need 1” conduit for more than 2 strands of 6 gauge. |
|
#2 posted 1544 days ago |
I could have sworn you could run more #6 than that through 1 inch. Or is it because it’s PVC and not metal? -- Matt - My Websites - http://www.bestinwood.com - Hand Tools :: http://www.workshopgarage.com - Small Shops |
|
#3 posted 1544 days ago |
I am not an electrician but I work around electric as a remodeling contractor. I go along with Marcb in that the 1” is not large enough to fit the 6 gauge wire. I know that there are some electricians floating around on LJ. -- Todd A. Clippinger, Montana, http://americancraftsmanworkshop.com |
|
#4 posted 1544 days ago |
first of all, don’t try it! according to the national electric code, you can only run a maximum of 2 #6 wires in 1” pvc. you’ll need to replace the underground raceway and up size your pvc to at least 1 1/4” to handle 6/3 however, if ever presented with this problem in the future, there’s simple way to do it. unhook the 12/3 on both ends from your panels. you then securely attach the 6/3 to one end of the 12/3, and use the 12/3 to pull the 6/3 through the pvc raceway. if there’s alot of bends in the raceway and it pulls hard, you can use aqua-gel, it’s a lubricant for pulling wire. |
|
#5 posted 1544 days ago |
ps. the conduit material does matter. you can run 3 #6 wires in metal conduit (EMT). however, being that your installation is underground, you have to use pvc. |
|
#6 posted 1544 days ago |
Hi Matt -- Mike --www.midlothianwoodworks.com |
|
#7 posted 1544 days ago |
I can help you with this as I was an electrician for a lot of years and just did a job at my house. I will reply PM latere. |
|
#8 posted 1544 days ago |
Sweet! Thanks! It will be another month or so before I do this anyway. I just eyeballed the size. I guess I should have gone out there and measured them. The wire running into my main panel doesn’t have the designation on it for that underground burial stuff so I assumed it was in conduit all the way out there. The neighbors in my subdivision have said their’s was in conduit as well. (All the same builder). I hope they are right. Thanks wdkits. Very good news. :) -- Matt - My Websites - http://www.bestinwood.com - Hand Tools :: http://www.workshopgarage.com - Small Shops |
|
#9 posted 1543 days ago |
1. If you don’t have a permit…get one or get a licensed electrician to do the job who will get a permit. Don’t even think about running underground service to your shop without a permit. 2. Code requires the pvc to be buried to a depth of 18”. If your going very far, get someone with a backhole to dig the trench. If you are doing the work yourself the inspector will need to see the trench to verify depth. 3. Put in 2 1/2” PVC conduit. This is large enough to handle a 200 amp service and will be easier to run the cable. 4. Make sure you handle the ground on the panel in the shop according to code. If you are running the shop panel as a subpanel off the house main you will need to separate the neutral and ground circuits. You may or may not need a ground rod at the shop. Depends on what the inspector says and code. You may need power disconnect on the outside of the shop. Depend on what the inspector says. If your are going to do your own work. Get a permit and meet with the inspector assigned to your job and talk over you plans and then do what the inspector tells you to do. I did the wiring on my show and that is how I when about planning the job. -- DaveH - Boise, Idaho - “How hard can it be? It's only wood!” |
|
#10 posted 1543 days ago |
That size wire through 1”.. I can’t imagine pulling that through that small opening or for that matter getting it into it in the first place. You didn’t mention the length or terrain. Ever think of running an overhead wire from your eaves? It’s legal. -- The smell of wood, coffee in the cup, the wife let's me do my thing, the lake is peaceful. http://gagnerwebsite.com/Deceiver/Craftsman_on_the_lake/Craftsman_on_the_lake.html |
|
#11 posted 1543 days ago |
You can not fill more than 80% of the conduit by code so my advice to you is get a 125 AMP sub panel (lug) with a 100 AMP main in the master panel and run #2 / 3 wire with ground (use UF) and also a 10 foot ground bar outside near the sub panel and no, its not over kill for a shop that has a number of 220 VAC machines as well as high current draw on the 110 equipment. Its cheaper to do it this way now because the load center the wire and breaker is not that much more then what you are buying now for the upgrade. Also check your code they may require you to use metal pipe for inside a shop. 6 gauge would only handle around 45-50 amps safely on a fun of 80 feet. Your UF rated wire which can be buried under ground should never be run in conduit due to heat build up. |
|
#12 posted 1543 days ago |
You know what? You guys have convinced me to wait until later in the season (maybe fall) and do this job right. All my existing wiring is down right now and I’ll be surface mounting it this week. I have survived out there on a single 20 amp circuit. At the beginning of my renovation I found second 20 amp circuit that was only running a single light bulb and the garage door opened. Never had a single problem. Even running my 1.75hp TS and 1hp DC at the same time. I was looking for an easy 220 but think I would probably be looking to upgrade in another year or so. This is exactly what I was looking for! Thanks for showing me the light! -- Matt - My Websites - http://www.bestinwood.com - Hand Tools :: http://www.workshopgarage.com - Small Shops |
|
#13 posted 1543 days ago |
I will be getting my 40 year pin from the IBEW next week. I will say there are some interesting ideas here! If you want to know how to use the existing wiring to do what ever you need to do, send a PM. The national electric code was changed last time or the time before to require a ground rod at each building even if a gound wire is pulled to the seperate building. The coundit under the bell box is 3/4”. -- "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence |
|
#14 posted 1543 days ago |
hey go over kill on it i ran 3 2” runs from the house to the shop and ended up useing them all run them below frost line i ran pex thru one of mine so i could have water part of the year. -- I buy tools so i can make more money,so ican buy more tools so I can work more, to make more money, so I can buy more tool, so I can work more |
|
#15 posted 1543 days ago |
It never hurts to put in lots of big conduits while the ditch is open. Seems like youi always find a way to use them up & wish for more :-)) -- "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence |
|
#16 posted 1474 days ago |
I have a question regarding fishing wire through a 1” conduit from the house to the garage. The previous owner ran only 2 hot wires (Red 10 gauge) and a green ground wire. He failed to run a white neutral wire for the sub-panel. I have two conduits with two seperate circuits from the house with 220 in one conduit and 110 in the other conduit. I want to ask what is the best way to run the other wire from the house to the garage in the conduit? I have posted a few pictures to show what I have. Sorry I have to figure out how to attach my pictures stay tune. |
|
#17 posted 1474 days ago |
If you don’t have or want to buy a fish tape, tie a good strong twine string on the existing wires, pull them out, tie on the new ones and pull them all back in. If you fish with the existing wire in the conduit, there is a slim chance yhio uwill damage them, but it usually doesn’t happen unless you have a lot of trouble. The important part of pullin ghte wire back in is the guy feediing it into the conduit and the guy on the other end not trying to go to fast and breaking it off. Hope that helps, good luck ;-)) -- "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence |
|
#18 posted 1474 days ago |
I have a 50’ tape and now have pics of the conduit. Would you suggest I try to use the fish tape in the existing conduit with the 220 wiring TopamaxSurvivor? |
|
#19 posted 1474 days ago |
The only pics I see are the ones that have always been on this thread. You can do it either way, If the fish tape goes through, just do it. If you have trouble getting it through, use the existing wire as a pull string as described. Good luck. -- "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence |
|
#20 posted 1466 days ago |
think i’ll stick to night crawlers |
|
#21 posted 1466 days ago |
Did you get this done matt? -- "some old things are lovely, warm still with life ... of the forgotten men who made them." - D.H. Lawrence |