Posted on Electrician Question: EDIT: 5 hp 19.5 amp Balder, can I use 12-2 and double pull 20 amp breaker

View toolie's profile

toolie

1739 posts in 1256 days


#1 posted 690 days ago

regarding the wire size, a 20A circuit (either 110v or 220v), usually sized to 80% of capacity, would be right on the edge of its ability to support that motor. any electrician worth his salt would, i believe, counsel that a 30A circuit and 10-2 wire be used.